Permit: T02EL00357

Parcel: 140373490

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
04/04/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
04/01/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*NO GREEN TAG.
03/20/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*PLEASE CORRECT THE FOLLOWING 1.) USE A PERMANENT MEDIA (SUCH AS MAGIC MARKER) TO IDENTIFY THE CIRCUIT BREAKERS PENCIL IS NOT ACCEPTABLE. 2.) THE CONDUCTORS FROM THE 100 AMP. SUBPANEL TO THE 100 AMP. MAIN CIRCUIT BREAKER MUST BE #3 COPPER. THE #4 COPPER CONDUCTORS YOU INSTALLED ARE ONLY RATED TO A MAXMUM 95AMPS. 3.) THERE IS NO GREEN TAG ON SUB FEED CONDUIT AT THIS TIME STATE APPROVAL IS REQUIRED BEFORE WE CAN ACCEPT THE WORK.