Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/28/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR NICE JOB. |
| 02/25/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) GROUND RODS TO BE ON SAME SYSTEM FOR A SUPLIMENTAL ROD FOR THE GROUNDING ELECTRODE SYSTEM OR PROVIDE A READING OF 25 OHMS OR LESS FOR A SINGLE ROD.W.) LOAD CONDUCTORS NOT TO EXIT THROUGH TOP END WALL OR AREA AS PER MANUFACTURE INSTRUCTION. THERE IS LIVE BUSS IN THIS AREA THAT CAN NOT BE DE ENERGIZED FOR WORK 3.) PLEASE IDENTIFY NEUTRAL CLOSER TO WETHER HEAD 4.) NEED PERMANENT METAL ADDRESS LABEL.. |