Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*NOTE B & 6 ELECT DRIVE GROUND RODS TO GRADE OR PROTECT ABOVE GRADE. |
| 02/15/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE PROVIDE GROUNDING ELECTRODE SYSTEM. BONDING IS OK, WE NEED 2 GROUND RODS AND CONNECT TO GROUNDED CONDUCTOR ART 250. |