Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/22/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR 2518, 2520,2522 FOR TEMP POWER OK CABLE DROP CALL FOR FINAL AFTER TIE IN. |
| 03/20/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) CANNOT OPEN GUTTER FOR ACCESS AND INSPECTION 2.) WATER AND GAS BONDING TO BE AS PER CODE 250-104 |
| 03/18/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245* 1.) TAPPING OF 4 CONDUCTORS ON SPLIT BOLT NOT APPROVED PER LISTING 110-3 NEC. 2.) GAS PIPING BONDING TO BE BONDED TO SERVICE EQUIP. PER 250-104-B.C. 3.) WATER PIPE BONDING TO BE BONDED AT EACH DWELLING UNIT. 4.) MAIN BONDING TUMPER TO BE INSTALLED TO NEUTRAL/GROUND BAR IN EACH SERVICE LOAD SIDE PER ART 250-24-1 5.) BOND BUSHING EQUIP GROUND AT OFFSET NIPPLE TO BE BONDED TO ENCLOSURE PER 250 NEC.6.) MULTI TAP SPLICE CONNECTORS IN GUTTER TO BE BRACED SO AS NOT TO HAVE SPRING TENSION ON GUTTER COVER. |