Permit: T02EL00306

Parcel: 115043890


Addresses:

1140 N 2ND AV


Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T02EL00306

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
03/08/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000* OK FOR CABLE DROP ONLY SO TRENCH CAN BE COVERED. THERE WILL BE NO METER CLEARANCE UNTIL A PERMIT IS OBTAINED FOR ALL INSIDE WORK ELECTRICAL, PLUMBING, MECHANICAL & BUILDING.) WILL VERIFY WATER BOND AND GAS BOND PRIOR TO RELEASE OF SERVICE.
03/05/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999* 1.) THE GROUNDING ELECTRODE CONDUCTOR IS TO BE CONTINOUS FROM THE NEUTRAL TERMANACE TO THE GROUND RODS. ANY SPLICES HAVE TO BE MADE BY AN IREVERSABLE METHOD. 2.) PLEASE USE HOLE IN GROUND CLAMP THAT HAS BEEN PROVIDED ON ALL CLAMPS.
02/20/2002 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*CUSTOMER WANTED CODE COMPLIANCE INFORMATION ON SERVICE CHANGE OH TO UG.