Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/15/2002 |
ELECTRIC - FINAL |
|
Approved |
|
| 02/13/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PLEASE VERIFY WATER AN GAS BONDING CAN NOT LOCATE 2) PLEASE VERIFY GROUND RODS CAN NOT LOCATE. 3.) MAIN BREAKER IS TO HAVE A HOLD DOWN CLIP/SCREW. 384-16. 4.) ROOF CLEARANCE IS TO BE MAINTAINED ACCROSS ROOF TO THE SOUTH 230-24. 5.) PLEASE INSTALL A WEATHER PROOF COVER ON THE RECEPTACLE ON THE NORTH SIDE OF THE HOUSE |