Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02EL00268

Parcel: 106011190


Addresses:

510 E SMOOT DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/27/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
02/07/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) I CAN NOT LOCATE THE GROUND RODS PLEASE VERIFY LOCATION 2.) SUB PANEL NEUTRAL CONDUCTOR NEED TO HAVE ALL STRANDS TEMANATED. WE HAVE CUT OFF SOME STANDS 3.) GROUNDING EQUIMENT CONDUCTOR TO BE THE SAME SIZE TO CARRY LOAD. WE HAVE A #12 SPLICED TO A #8 CONDUCTOR.4.) WHAT IS THE #10 CABLE COILED UP ATT HE SIDE OF THE HOUSE FOR?