Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02EL00253

Parcel: 115060590


Addresses:

26 W VENTURA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/12/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR
03/03/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) GROUND RODS TO BE 6' APART 2.) A BONDING DEVICE IS NEEDED AT OFFSET NIPPLE IN METER SCOKET 250-94. 3.) MAIN BACK FEED BRAKER TO HAVE HOLD DOWN DEVICE AS PER MANUFACTURES REQUIREMENTS 384-16.
02/22/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*LOCKED DENIED.