Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/25/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR INCREASE OK CABLE DROP. |
| 02/14/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) GROUND RODS MUST BE SPACED MIN 6' APART PER ART 250 NEC. ALSO GROUNDING ELECTRODE CONDUCTOR TO BE UNSPLICED 2.) GAS AND WATER PIPING REQUIRED TO BE BONDED. 250-104 NEC. 3.) NEW ELECTRIC SERVICE CANNOT BE INSTALLED OVER GAS METER 110-26 NEC. 4.) SPACE FOR HGIHEST OVER CURRENT DEVICE OR BREAKER NOT TO EXCEED 6'7". 5.) CHASE NIPPLES WITH REDUCTING WASHERS NOT ALLOWED SHOULD BE CLOSED NIPPLE WITH LOCKNUTS BOTH SIDE OF ENCLOSURE WITH BOND BUSHING. 250-94 NEC. 6.) CONDUCTS TO BE STRAPPED TO STRUCTURE. |