Permit: T02EL00249

Parcel: 123021520


Addresses:

2826 E EDISON ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/25/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR INCREASE OK CABLE DROP.
02/14/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*1.) GROUND RODS MUST BE SPACED MIN 6' APART PER ART 250 NEC. ALSO GROUNDING ELECTRODE CONDUCTOR TO BE UNSPLICED 2.) GAS AND WATER PIPING REQUIRED TO BE BONDED. 250-104 NEC. 3.) NEW ELECTRIC SERVICE CANNOT BE INSTALLED OVER GAS METER 110-26 NEC. 4.) SPACE FOR HGIHEST OVER CURRENT DEVICE OR BREAKER NOT TO EXCEED 6'7". 5.) CHASE NIPPLES WITH REDUCTING WASHERS NOT ALLOWED SHOULD BE CLOSED NIPPLE WITH LOCKNUTS BOTH SIDE OF ENCLOSURE WITH BOND BUSHING. 250-94 NEC. 6.) CONDUCTS TO BE STRAPPED TO STRUCTURE.