Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/10/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 04/05/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) WIRE TO SUBPANEL NOT INSTALLED YET. 2.) NEED TO INSPECT CONNECTIONS BOTH ENDS OF FEEDER WIRING TO SUBPANEL. 3.) INSTALLATION OF ROMEX OK BOXES OK RECALL FOR INSPECTION WHEN DONE. 4.) ALSO BECAUSE SHOP BLD. IS SEPERATE FROM HOUSE (NOT ATTACHED BY STRUCTURE) 2 GROUND RODS ARE REQUIRED BY CODE AND GROUNDED TO SUB PANEL PER 250-32 NEC. GROUND RODS TO HAVE 6' MIN SPACING APART. |