Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/13/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 02/08/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*STUMP IN FRONT OF SERVICE EQUIPMENT MUST BE REMOVED. A REINSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION. |
| 02/06/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) RODS TO BE FLUSH OR BELOW GRADE 2.) BURRY GROUND WIRE 3.)STRAP GROUND WIRE FIRMLY TO WALL 4.) FRONTAL CLEARANCE FO RSERVICE INCLUDED ALL VIGITATION; STUMPS AND BLOCK BORDERING. 5.) USE 1/4: HARDWARE MIN TO MOUND SERVICE AND SUPPORT RISER (EG LAG BOLTS) BLOCK USED FOR BACKING OF RISER SUPPORT TO BE PAINTED (WEATHER TREATED. 6.) HIGHEST BREAKER SPACE EXCEDER 6-7" 7.) NEED TO CHECK IF ALL CIRCUIT IN INTERIOR ARE RATED AT 20 AMPS. |