Permit: T02EL00234

Parcel: 14024058J


Addresses:

1111 E WIEDING RD

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
02/26/2002 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
02/20/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*DENIED: 1.) I.D. ALL KITCHEN PROTECTED GFCI RECEPTACLES ALSO IF THERE IS NO EQUIPMENT GROUND TO THESE RECEPTACLES IT MUST BE LABELED AS SUCH. 2.) THE DRY WALL REMOVED FROM THE CEILING IN THE BACK ROOM HAS EXPOSED OTHER CODE VIOLATIONS. CODE VIOLATIONS A.) CONCEALED JUNCTION BOXES MUST BE EXPOSED FOR PROPER ACCESS. B.) SINGLE CONDUCTOR AND NO ROMEX CLAMP AT AREA ABOVE EXIT DOOR AND AREA ABOVE BATHROOM DOOR
02/07/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*INSTALLED GROUNDING STYLE RECEPTACLER IN AN UNGROUNDED SYSTEM. REINSTALL TWO WIRE RECEPTACLER OR YOU MAY IMPLEMENT OTHER CODE ALTERNATIVES. THE KITCHEN COUNTER TOP RECEPTACLER WILL ALSO REQUIRE GFCI PROTECTION. CONDUIT SUBJACENT TO SERVICE EQUIPMENT WILL HAVE TO BE IDENTIFIED AS TO THEIR DESTINATION AND IF UNSAFE OR GOING OUT OF THE PROPERTY WILL NEED TO BE ARRANGED TO RENDER INSTALLATION NOT USEABLE. WILL NEED A PERMANENT ADDRESS TAG AT SURVIRE EQUIPMENT.A LICENSED C-11 ELECTRICAL CONTRACTOR WILL BE REQUIRED TO MAKE ALL NECESSARY CORRECTIONS PLEASE CALL 791-5550 X 136 AND LEAVE NAME AND TELEPHONE NUMBER OF C-11 ELECTRICAL CONTRACTOR BEFORE NEXT INSEPCTION.