Permit: T02EL00227

Parcel: 112070220

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/14/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES PLEASE SEE WRITE UP FROM PREVIOUS INSPECTION. ON 2/7/02.
02/07/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) ADDRESS LABEL TO BE SCREWED OR RIVITED TO ENCLOSURE. 230-70 NEC #9287 CITY ORDIN. 2.) ALL CIRCUIT BREAKERS TO BE OF SAME MANUFACTURE TYPE AS PANEL 110-3 NEC. 3.) LOCATE 2ND GROUND ROD AND EXPOSE CLAMP FOR INSPECTION.