Permit: T02EL00226

Parcel: 126163470

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/08/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR
03/05/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0215* 1.) SERVICE RISER CONDUIT BUSHING MUST BE GROUNDED TO BOX OR NEUTRAL BAR. 2.) NOTE CHANGE ON PLAN REGARDING HOUSE PNAEL AND UNIT 1. CHANGE MARKING/ADDRESS TO 452 N. COLUMBUS HOUSE PNL. AT MAIN BREAKER. 3.) MACK HOUSE PANEL ON EXTERIOR. 4.) BOND GAS PIPING TO SERVICE EQUIPMENT, OR COLD WTR. TO GAS PIPE AT WTR HTR. ALL SCREWS LEFT IN MAIN PANEL BOTTOM COMPARTMENT LEAVE OFF FOR NEXT INSPECTION. AT GAS METER MOVE GROUND WIRE TO THE HOUSE SIDE PIPE.
02/14/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0215*1.) THIS IS NOT A SIMPLE UPGRADE OF CHANGING A 125A SINGLE METER FOR A 200A SINGLE METER. 2.) THE NEW SERVICE EQUIPMENT HAS THREE (3) METER POSITIONS. THIS INDICATES THE SECTIONING OF THE BUILDING TO THREE TENANTS. 3.) SUBMIT A PLAN DETAILING THE PARTITIONING DIVIDING OF THE BUILDING, THE SEPARATION OF INTERIOR WIRING, THE LOCATION OF THE NEW INTERIOR PANELS. 4.) ALWAYS LEAVE ALL JOB DOCUMENTS ON SITE. THANKS.