Permit: T02EL00223

Parcel: 110030890

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL00223

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) ALL CORRECTIONS COMPLETED
04/22/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
02/01/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*AT METER PANEL CHK. W SUBA. 1.) NEUTRAL AND GROUND CONDUCTORS MUST BE ISOLATED AT THE OUTSIDE AND INSIDE BRAKERS BOXES. 2.) INSTALL A 4 WIRE APPROVED TYPE SUPPLY CORD FROM OUTSIDE BREAKER OX TO INTERIOR BREAKER BOX. 3.) EXPOSED WIRES AT OUTSIDE BREAKERS BOX MUST BE PROTECTED IN SHCD.80 PVC CONDUIT OR EAUIVALENT.
01/31/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
01/31/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*UNIT LOCKED COULD NOT INSPECT INTERIOR PANEL.