Permit: T02EL00223

Parcel: 110030890

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Permit Number - T02EL00223

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Denied

Date Description Inspector Results Comments
04/22/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) THE 125A PANEL OUTSIDE IS NOT APPROVED TO HAVE THE TRAILER RECEPTACLE INSTALLED INSIDE OF IT IT MUST BE INSTALLED IN ITS OWN OUTLET BOX. 2.) SEAL THE ONE INCH HOLE BEHIND TH EBOX 3.) THE LAST INSPECTOR REQUESTED THAT THE ROMEX BELOW THE WINDOW OUTSIDE PORTCH AREA BE PROTECTED IT CANNOT BE RUN OUT IN THE OPEN. 4.) THE SHED WIRING IS UNAPPROVED ALL WIRING HAS TO BE PROTECTED 5.) THE NEUTRALS IN THE INSIDE PANEL NOT TERMINATED IN PANEL 6.) PROTECT ALL WIRING IN CLOSETS. 7.) INSTALL SMOKE DETECTORS IN BEDROOM. 8.) OBTAIN AN ELECTRICAL C-11 CONTRACTOR TO MAKE CORRECTIONS AND CHECK ALL OTHER ELECTRICAL.
02/01/2002 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection 0000*