Permit: T02EL00218

Parcel: 13106017A


Addresses:

5522 E 32ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/31/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*1.) THE ELECTRICAL SERVICE SERVICE EQUIPMENT AND LOAD CENTER PANEL MUST BE ACCESSIBLE TO THE TENANT AND MUST HAVE HAVE A MINIMUM OF THREE (3) FEET OF CLEAR WORKING SPACE IN FRONT 2.) ELECTRICAL CIRCUIT BREAKERS MUST BE MARKED WITH AREA SERVED. CORRECTED BY TENANT ON SITE.