Permit: T02EL00211

Parcel: 107120230


Addresses:

2901 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T02EL00211

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2002 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*
05/16/2002 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*1.) PLEASE MAINTAIN WORKING CLEARNACE IN FRONT OF SERVICE & DISCONNECTS 2.) PLEASE VERIFY GROUNDING ELECTRODE 3.) DISCONNECT SWITCHES NEED TO BE LABELED. 4.) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDING CONDUCTOR 5.) NM CABLE TAPED INTO JUNCTION BOX 6.) UNDERGROUND COVERED WITHOUT INSPECTION PLEASE OPEN FOR INSPECTION. 7.) PLEASE PROVIDE JOB PLANS ON SITE.