Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL00192
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR. | |
02/01/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) INSTALL PERMANENT ADDRESS LABEL, MSUT BE SCREWED OR RIVITED TO SERVICE ENCLOSURE 230-70 N.E.C. #9287 CITY AMENDMENTS. 2.) INSTALL 2 GROUND RODS 6' MIN APART. PER ART 250 N.E.C. 3.) SUPPORT RISER CONDUIT WITHIN 3' OF RISER HUB. 4.) SUPPORT RECEPT. BOX BELOW PANEL AND 1" CONDUIT BELOW AND ABOVE. 5.) EQUIP. GROUNDING MUST BE GREEN OR BARE. 250-119. NEC. 6.) #8 WIRE MUST BE ON 50 AMP BREAKERS. ART 310 NEC. 7.) CARFLEX USED AS A RACEWAY FOR AC UNIT NOT APPROVED, MUST SCH. 80 IF PVC OR STEEL CONDUIT. PER #9287 CITY AMENDMENTS. 8.) BOND WATER & GAS PIPING. |