Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL00175
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
02/01/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TO ENERGIZE UNDER CONTROL OF ELECTRICAN 1.) PROTECT CABLE IN AREAS OF PEOPLE TRAFFIC 2.) PLEASE PROVIDE STRAIN RELIEF FOR CORDS TO SUB PANELS. | |
01/30/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TO CLEAR POWER. WILL NEED TO SEE SERVICE RV CONNECTIONS. | |
01/28/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) BONDING DEVICES ARE NEEDED FOR BOTH SIDES OF NIPPLES AT THE SERVICE 250-94. 2.) BONIDING DEVICES ARE NEEDED FOR THE METAL CONDUIT CONTAINING THE GROUNDING ELECTRODE CONDUCTOR 250-64. 3.) PLANS CALL FOR 10' MINIMUM BETWEEN GROUND RODS THEY ARE SPACED 6' APART. THANK YOU HAVE A NICE DAY CK FAULT CURRENT RATING FOR MAIN BREAKERS. |