Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/05/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 02/01/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK TO ENERGIZE UNDER CONTROL OF ELECTRICAN 1.) PROTECT CABLE IN AREAS OF PEOPLE TRAFFIC 2.) PLEASE PROVIDE STRAIN RELIEF FOR CORDS TO SUB PANELS. |
| 01/30/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR POWER. WILL NEED TO SEE SERVICE RV CONNECTIONS. |
| 01/28/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) BONDING DEVICES ARE NEEDED FOR BOTH SIDES OF NIPPLES AT THE SERVICE 250-94. 2.) BONIDING DEVICES ARE NEEDED FOR THE METAL CONDUIT CONTAINING THE GROUNDING ELECTRODE CONDUCTOR 250-64. 3.) PLANS CALL FOR 10' MINIMUM BETWEEN GROUND RODS THEY ARE SPACED 6' APART. THANK YOU HAVE A NICE DAY CK FAULT CURRENT RATING FOR MAIN BREAKERS. |