Permit: T02EL00154

Parcel: 134170180


Addresses:

7245 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/07/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR SENT TO TEP ON 10/8/02 AT 9:15AM.
04/10/2002 ELECTRIC - FINAL Denied CORRECT THE FOLLOWING 1.) RUN A #4 BARE COPPER GROUND WIRE FROM THE COLD WATER MAIN PIPE TO THE GAS PIPE AND INTO PANEL GROUND BARE. 2.) THE INDEX I.D. FOR CIRCUIT BREAKERS MUST BE MARKED WITH AREAS SERVED, E.G. KITCHEN, LIV RM, ETC... 3.) USE METALL NUMBERS FOR ADDRESS ON PANEL 4.) INSTALL 3" HIGH ADDRESS #'S ON HOUSE 5.) INSTALL LANDING CLEVIS FOR TEP. SERVICE CONDUCTORS. 6.) INSTALL TWO (2) PIPE CLAMPS ON RISER PIPE. 7.) INSTALL BRACE FOR RISER ABOVE ROOF.