Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/20/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/14/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0215*THE CODE REQUIRES A MINIMUM OF TWO STRAPS ON THE SERVICE RISER CONDUIT. THE STRAPS MUST BE ATTACHED TO THE STRUCTURE" AND PROPERLY SIZED TO THE COUNDIT. YOU HAVE ATTACHED THE STRAPS TO THE (1) FACIA AND TO THE (2) ROOF SHEATHING. NEITHER OF THESE ARE STRUCTURAL MEMBERS I SUGGEST YOU USE UNISTRUT STANDOFFS WITH THE PROPER STRAPS THIS APPLIES TO BOTH RISER CONTACT TEP TO HAVE METERS SET. THE TAKING OF ELECTRIC POWER IS ILLEGAL. |
| 01/29/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*USE A ROMEX CONNECTOR WHERE #4 GROUND ENTERS BOTTOM TO SEAL OPENINGS. |