Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL00114
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/08/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*C.S. CLEAR IS BOND REQUIRED AND HAS IT BEEN POSTED? DENY CLEARANCE IF THIS REQUIREMENT HAS NOT BEEN MET. THANK MAC. | |
03/05/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*THE 2 1/2" STEEL RISER CONDUIT MUST BE FITTED WITH A GROUNDING BUSHING AND A GROUND WIRE CONNECTING IT TO THE METAL OF THE PANEL. 2.) EXPOSE THE TWO GROUND ROD ENDS ENOUGH TO ALLOW INSPECTION OF THE CLAMPS. 3.) USE REDUCING BUSHINGS ON THE OFFSET NIPPLE END AT THE RELAY 'J' BOX TO SEAL OFF WATER. 4.) USE A "SEAL TIGHT" CONNECTOR TO TERMINATE THE SEAL TIGHT FLEX TO THE 'C' CONDULET AT THE IRRIGATION TIME CLOCK BOX 5.) POST BOND WITH CITY DEVELOPMENT SERVICES FOR CONNECTION OF POWER 6.) MARK THE CIRCUIT INDEX ( WITH AREA SERVED INSIDE THE PANEL COVER. CORRECT ALL OF ABOVE AND RECALL INSPECTION. | |
01/22/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*CANNOT ISSUE POWER FOR TEMP CONSTRUCTION UNTILL A PERFORMANCE BOND IS POSTED THUR OUR OFFICE FOR THIS JOB THIS A COMBO PERMIT. OR BUILDING FINALED. |