Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/18/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) ELECTRICAL SERVICE REQUIRES 3' OF CLEARANCE IN FRONT OFF BUSH HAS TO BE REMOVED. 2.) THE 30 AMP CIRCUIT RUN OUTSIDE OF THE SERVICE TO INSIDE HAS TO BE INSTALLED IN A PROPER MANNER IT IS NOT HAS TO BE INSTALLED IN A PROPER MANNER IT IS NOT ALLOWED OUTSIDE PHYSICALLY UNPROTECTED. 3.) REAR OUTSIDE LIGHT TO BE REPLACED 4.) INSIDE KITCHEN RECEPTALES BY SINK TO BE GFI TYPE, GROUND FAULT INTERRUPTER. TWO OF THEM 5.) AT FUSE BOX INSIDE CLOSET #12 WIRE CIRCUITS TO BE FUSED AT 20AMPS ONY, #14 WIRE CIRCUITS AT 15AMPS 6.) REMOVE ILLEAGLE WIRING BELOW FUSE PANEL IN CLOSET AND INSTALL WIRING RESECURE BOX, ROMEX WIRING NOT TO BE OUT IN OPEN. 7.) ONE SMOKE DETECTOR IN HALL WAY COMMON TO ALL BEDROOMS OR ONE IN EACH BEDROOM REQUIRED BATTERY OK 8.) WIRING IN FURNACE ROOM TO BE CORRECTED AN CLEANED UP SINCE HOUSE IS VACANT OBTAIN THE SERVICES OFF A LICENSED ELECTRICAL CONTRACTOR TO CORRECT AND RECALL FOR INSPECTION. |