Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/18/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP. TEP CLEARED RISER HEIGHT PER ELECTRICAL.
01/15/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) SUPPORT RISER WITHIN 3' OF SERVICE ENCLOSURE. 2.) INSTALL PERMANENT ADDRESS LABEL SCREWED OR RIVITED TO ENCLOSURE. #9387 CITY ORDIN. 3.) N.E.C. STATES, THERE MUST BE 8' MIN OF GROUND ROD IN EARTH. GROUND RODS APPREAR TO BE CUT, COULD NOT LOCATE SER # AT TOP OF RODS. EXPLAIN? 4.) HIEGHT OF RISER ABOVE ROOF NOT TO TEP SPEC. APPROVAL IS SUBJECT TO TEP APPROVAL. 5.) PLEASE LEAVE NAME & PH #LIC # OF CONTRACTOR DOING WORK.