Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL00073
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2002 | ELECTRIC - FINAL | Approved | ALL ITEMS INSIDE CORRECTED & APPROVED BY R HOLLANDER LAST ITEM WAS SUPPORT 3/4" PVC COMING OUT OF 30A DISCONNECT OUTSIDE (DONE.) | |
| 04/01/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*INTERIOR PANEL OK 1.) PLEASE INSTALL FUSES 2.) SUPPORT 3/4" CONDUIT. | |
| 03/14/2002 | ELECTRIC - FINAL | Denied | 1. INSTALL PVC CONNECTOR AT DISCONNECT ON 3/4" PVC INTO SWITCH 2.) FUSE AT 30AMS NOT 100AMP. 3.) INTERIOR PANEL INSTALLED INCORRECTLY GROUND NOT TIED IN TO BUS YELLOW WIRE SHOULD BE USED AS NEUTRAL BUT TIED INTO HOT CABLES MUST BE CLAMPED INTO BOX. CANNOT SPLICE #12 WITH TAPE ONLY NEED WIRE NUT THERE ARE ALL 20AMP BREAKERS WHERE ARE THE 15AMP IMPROPER INSTALLATION AT REAR OF PANEL TO J-BOX. SUGGEST YOU OBTAIN A C-11 ELECTRICAL CONTRACTOR TO MAKE CORRECTIONS | |
| 01/27/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 01/23/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0215*THE CABLE FROM THE METER PANEL MUST BE LISTED FOR MOBILE HOME USE. TYPE NM CABLE IS NOT ALLOWED FOR THIS USE. DOORS LOCKED. COULD NOT INSPECT INTERIOR PANEL. | |
| 01/15/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) CHANGE INTERIOR PANEL TO ACCOMODATE THE ADDITIONAL CIRCUITS 2.) CHANGE FUSES IN MAIN PANEL TO 30 AMP. OR TO CORRESPOND WITH NEW WIRING. |