Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL00063
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*GATE LOCKED. WILL RESUME TOMORROW. | |
01/24/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0210*MAIN GROUNDING ELECTRODE CONDUCTOR MUST BE DIRECTLY ATTACHED TO THE NEUTRAL BAR A REFEE IS DUE BEFORE THE NEXT INSPECTION. | |
01/17/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) MAIN GROUNDING ELECTRODE CONDUCTOR MUST ATTACH W/OUT SPLICE DIRECTLY TO THE NEUTRAL TERMINAL BAR. |