Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/24/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 01/17/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) EQUIP. GROUND TO BOND LOCKNUTS UNDERSIZED SEE ART 250-122 N.E.C. |
| 01/11/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) GROUNDING ELECTRODE CONDUCTOR SPLICE TO BE IRRIVERIBLE CRIMP OR EXOTHERMIC, ART 250-50 NEC 2.) INSTALL BOND BUSHING WHERE USING RW'S AT BOTTOM OF PANEL 3.) INSTALL BOND BUSHING ON 1 1/2" CONN. FOR SHOP FEEDER. BOTH ENDS. ART 250-96 / 300-4 N.E.C. 4.) INSTALL BOND BETWEEN NEUTRAL AND GROUND BAR AT SUB PANEL (SHOP) 5.) BOND GAS PIPING.6.) OBTAIN PERMIT FOR NEW ELECTRICAL WIRING FOR SHOP. |