Permit: T02EL00058

Parcel: 122060110


Addresses:

2107 N CATALINA AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/24/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
01/17/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) EQUIP. GROUND TO BOND LOCKNUTS UNDERSIZED SEE ART 250-122 N.E.C.
01/11/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) GROUNDING ELECTRODE CONDUCTOR SPLICE TO BE IRRIVERIBLE CRIMP OR EXOTHERMIC, ART 250-50 NEC 2.) INSTALL BOND BUSHING WHERE USING RW'S AT BOTTOM OF PANEL 3.) INSTALL BOND BUSHING ON 1 1/2" CONN. FOR SHOP FEEDER. BOTH ENDS. ART 250-96 / 300-4 N.E.C. 4.) INSTALL BOND BETWEEN NEUTRAL AND GROUND BAR AT SUB PANEL (SHOP) 5.) BOND GAS PIPING.6.) OBTAIN PERMIT FOR NEW ELECTRICAL WIRING FOR SHOP.