Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/11/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 01/28/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) REPLACE OR RE INSTALLED BUSHING IN BACK OF PANEL. (COMING OUT.) 2.) INSTALL PERMANENT ADDRESS LABEL SCREWED OR RIVITED TO ENCLOSURE PER 230-70 #9287 CITY ORDIN.3.) ID ALL CIRCUIT BREAKERS 4.) NEW OUTSIDE RECEPTACLE TO BE GFCI MAKE CORRECTIONS AND RECALL INSP. |