Permit: T02EL00032

Parcel: 130120330


Addresses:

3802 E 32ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/28/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR.
01/25/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) ROUND 30-60 AMP METER BASES NOT ALLOWED FOR 125A SERVICE UPGRADE. 2.) SERVICE NOT GROUNDED 2 GROUND RODS 6' APART PLUS WATER LINE AND GAS LINE BOND. 3.) 1" PVC AT BOTTOM OF SERVICE TO BE SCHEDULE 80 AND MUST HAVE A CONNECTOR INTO BOX, SUPPORT PVC. 4.) CANNOT DOUBLE LUG GROUND WIRE AND NEUTRAL, TAPE NEUTRAL WHITE 5.) SERVICE NOT INSTALL PER 99 ELECT CODE.SUGEST YOU OBTAIN THE SERVICES OF AN ELECTRICAL LICENSED CONTRACTOR TO DO JOB 6.) NEED 2" RIGID MUST, WITH #4 COPPER CONDUCTORS 2' ABOVE ROOF 2 STRAPS AND WEATHER HEAD.