Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/28/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR. |
| 01/25/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) ROUND 30-60 AMP METER BASES NOT ALLOWED FOR 125A SERVICE UPGRADE. 2.) SERVICE NOT GROUNDED 2 GROUND RODS 6' APART PLUS WATER LINE AND GAS LINE BOND. 3.) 1" PVC AT BOTTOM OF SERVICE TO BE SCHEDULE 80 AND MUST HAVE A CONNECTOR INTO BOX, SUPPORT PVC. 4.) CANNOT DOUBLE LUG GROUND WIRE AND NEUTRAL, TAPE NEUTRAL WHITE 5.) SERVICE NOT INSTALL PER 99 ELECT CODE.SUGEST YOU OBTAIN THE SERVICES OF AN ELECTRICAL LICENSED CONTRACTOR TO DO JOB 6.) NEED 2" RIGID MUST, WITH #4 COPPER CONDUCTORS 2' ABOVE ROOF 2 STRAPS AND WEATHER HEAD. |