Permit: T02EL00010


Addresses:

3941 N 4TH AV #21

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
01/08/2002 ELECTRIC - RECONNECT Approved JUDITH DID THIS GET FEC YESTERDAY OR TODAY. PLEASE CLEAR FEC.
01/04/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) ELECTRIC PEDISTAL IS TOO FAR FROM HOME MOVE PEDISTAL OR PROVIDE A 30 AND PLUMG RECEPTACLE WITHIN 4' OF HOME IN REAR 1/3 OF SPACE. 2.) MOVING SEWER CONNECTION REQUIRED A PERMIT. 3.) RECEPTACLE IN PEDISTAL OR NEW RECEPTACLE MSUT BE PROPERLY GROUNDED. 4.) PROPER DEAD FRONT MUST BE INSTALLED IN PEDISTAL.