Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02EL00002

Parcel: 115022460


Addresses:

516 E SENECA ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/26/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
02/28/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*DENIED YOU MUST OBTAIN A PERMIT FOR ALL NEW WIRING PRIOR TO COVER UP ALSO NAME ELECTRICAL CONTRACTOR FOR UPGRADE MUST BE LICENSED KIT NEW WIRING.
01/28/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1.) PLEASE IDENTIFY THE NEUTRAL CLOSER TO THE WETHER HEAD 2.) PERMIT FOR INTERIOR WORK NEEDS TO BE UFERING BEFORE CROSS OVER. 3.) FINISH TERMANATIONS OF CONDUCTORS IN NEW PANEL. 4.) PLEASE STRAP GROUND TO THE BUILDING.
01/16/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) A PERMANENT METAL ADDRESS LABEL WILL BE NEEDED 2.) USE APPROVED FITTING TO CONNECT LB TO PANEL-AN EMT CONNECTOR IS NOT APPROVED OR IS A CHASE NIPPLE. 3.) LB ABOVE PANEL NEED TO HAVE THE COVER ACCESSABLE. 4.) PLEASE REMOVE SHEATHING UNDER FOR INSPECTION OF RISER SECORING. 5.) THERE ARE NO SERVICE CONDUCTORS INSTALLED AT THIS TIME. 6.) YOU WILL NEED TO BOND THE WATER AND GAS AS PER CODE 7.) PLEASE VERIFY PERMIT FOR INTERIOR WORK BEING DONE THERE ARE NEW CIRCUIT CABLES PULLED INTO NEW PANEL 8.) WORK IS TO BE DONE BY OWNER OCCUPANT OR A LICENSED CONTRACTOR UNIT IS UNOCCUPIED AS THIS TIME.