Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TEMP C OF O. 1.) GFI MISSING ON ROOF FOR REFRIG & FREEZER UNIT BACK SECTION. 2.) GROUND ROD IN FRONT OF SW GEAR POSES TRIP HAZARD, DRIVE TO GRADE ALSO TIGHTEN GROUND CLAMP. 3.) SWITCH GEAR SHOWING A NEW PANEL C 200A DISCONNECT, THIS IS NOT SHOW ON PLAN. 4.) PANEL SCHEDULES DO NO COINCIDE WITH ON SITE PLANS. 5.) PLEASE HAVE WENDY'S PROVIDE INFO ON KIT COUNTER TOP & LOOKING AGENT A FIND A LISTING ON PANEL ITSELF AND EQUIPMENT STAND IT SELF NOT ON WHOLE ITEM. 6.) INSTALL RECEP COVER ON DEVICE ABOVE SODA MACHINE. 7.) CORDS TO RESTROOM DOORS TO BE STRAPPED AWAY FROM DOOR OPENING ARMS 8.) K-4 LIGHTS AT NORTH & SOUTH SIDES OF BUILDING OUTSIDE MISSING. |
|
| 03/21/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* |