Permit: T02CM05964

Parcel: 12402009D


Addresses:

1005 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM05964

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TEMP C OF O.
1.) GFI MISSING ON ROOF FOR REFRIG & FREEZER UNIT BACK SECTION.
2.) GROUND ROD IN FRONT OF SW GEAR POSES TRIP HAZARD, DRIVE TO GRADE ALSO TIGHTEN GROUND CLAMP.
3.) SWITCH GEAR SHOWING A NEW PANEL C 200A DISCONNECT, THIS IS NOT SHOW ON PLAN.
4.) PANEL SCHEDULES DO NO COINCIDE WITH ON SITE PLANS.
5.) PLEASE HAVE WENDY'S PROVIDE INFO ON KIT COUNTER TOP & LOOKING AGENT A FIND A LISTING ON PANEL ITSELF AND EQUIPMENT STAND IT SELF NOT ON WHOLE ITEM.
6.) INSTALL RECEP COVER ON DEVICE ABOVE SODA MACHINE.
7.) CORDS TO RESTROOM DOORS TO BE STRAPPED AWAY FROM DOOR OPENING ARMS
8.) K-4 LIGHTS AT NORTH & SOUTH SIDES OF BUILDING OUTSIDE MISSING.
03/21/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*