Permit: T02CM05927

Parcel: 12605146H


Addresses:

1030 N ALVERNON WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/02/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/29/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0920*/ LEFT 2 MESSAGES FOR BPI - NO ANSWER. BUILDING LOCKED NO ACCESS.
07/24/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) FILL UNUSED OPENING IN BOX - CONNECTOR IS NOT A SEAL. 2) WHERE IS NEW ELECTRICAL PLAN? 3) M/C CABLE TO BE SUPPORTED AT 6' INTERVALS. 4) WHERE ARE OPEN SWITCHES?

A RE FEE IS BEING ACCESSED AS PER ADMINISTATIVE CODES DUE TO THE NUMBER OF INSPECTIONS.
04/14/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OPEN WALLS AT ALL NEW SWITCH AND RECEPTICAL LOCATIONS 2ND FLOOR. OK 1ST FLOOR WALL.
03/13/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) INSTALL ELECTRIC BETWEEN BOXES AS PER CODES.
2.) PLEASE HAVE PLANS STAMPED AND APPROVED WITH THE CITY AS IN #4 OF PREVIOUS.
03/05/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) WHO IS LICENSED L-11 ELECTRICAL CONTRACTOR?
2.) M/C CABLE TO BE SUPPORTED & STRAPED AS PER CODE.
3.) PLEASE MAKE ARRANGEMENTS FOR ELECTRICAL CONTRACTOR TO MEET ME HERE ON SITE.
4.) WHO IS RESPONSIBLE FOR ELECTRICAL DRAWINGS? PLANS STATE ARCHITECTIAL ONLY FOR STAMP.
02/07/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) AN LICENSED L-11 ELECTRICAL CONTRACTOR IS NEEDED TO PERFORM WORK.
2.) PLEASE OPEN UP AREAS OF WORK FOR INSPECTION.
3.) CEILING AREAS OF DEMOLITION TO BE OPENED TO INSPECT METHODS OF REMOVAL.