Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2003 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* SUBJECT TO 1 HOUR PARTITIONS BEING CHANGED. | |
| 10/09/2003 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* EAST DOOR NEEDS DEAD BOLT REMOVED AT EXIT-PROVIDE PROPER FIRESTOP FOR 1 HOUR PENETRATION. | |
| 10/02/2003 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*SEE WRITE UP FROM 10-1-03 LHANLY | |
| 10/01/2003 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) PROVIDE PROPER FIRESTOP FOR 1 HOUR PENETRATIONS 2) REMOVE DEADBOLTS FROM SECONDARY EXITS WITH PANIC BARS OR PROVIDE PANIC BARS THAT ALSO RELEASE DEADBOLT . 3) PROVIDE PROPER SIGNAGE (PER A.P.A.A.G.) FOR ACCESSABLE ROUTES AND RESTROOMS. 4) SWINGING DOOR TO WOMENS RESTROOM IS NOT ADA COMPLIANT. | |
| 04/14/2003 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*1.)PROVIDE APPROVED ELECTRIC FINAL. 2.) WHERE IS PAGE A2.5? PLANS INDICATE A 1 HOUR CORRIDOR, PLEASE INDICATE HOW YOU ARE GOING TO ACHIEVE A 1 HOUR RATING WITH WALLS THAT TERMINATE BELOW THE SUSPENDED CIELING. 3.) WHERE ARE PLANS/PERMITS FOR LOBBY ADDITION? |