Permit: T02CM05927

Parcel: 12605146H


Addresses:

1030 N ALVERNON WY

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/15/2003 BUILDING - FINAL Approved IVRS - Inspection 0000* SUBJECT TO 1 HOUR PARTITIONS BEING CHANGED.
10/09/2003 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000* EAST DOOR NEEDS DEAD BOLT REMOVED AT EXIT-PROVIDE PROPER FIRESTOP FOR 1 HOUR PENETRATION.
10/02/2003 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*SEE WRITE UP FROM 10-1-03 LHANLY
10/01/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) PROVIDE PROPER FIRESTOP FOR 1 HOUR PENETRATIONS 2) REMOVE DEADBOLTS FROM SECONDARY EXITS WITH PANIC BARS OR PROVIDE PANIC BARS THAT ALSO RELEASE DEADBOLT . 3) PROVIDE PROPER SIGNAGE (PER A.P.A.A.G.) FOR ACCESSABLE ROUTES AND RESTROOMS. 4) SWINGING DOOR TO WOMENS RESTROOM IS NOT ADA COMPLIANT.
04/14/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*1.)PROVIDE APPROVED ELECTRIC FINAL.
2.) WHERE IS PAGE A2.5? PLANS INDICATE A 1 HOUR CORRIDOR, PLEASE INDICATE HOW YOU ARE GOING TO ACHIEVE A 1 HOUR RATING WITH WALLS THAT TERMINATE BELOW THE SUSPENDED CIELING.
3.) WHERE ARE PLANS/PERMITS FOR LOBBY ADDITION?