Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 10/24/2003 |
ELECTRIC - PROGRESS |
|
Approved |
IVRS - Inspection 0000* |
| 10/01/2003 |
ELECTRIC - PROGRESS |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) A DISCONNECTING MEANS IS NEEDED FOR TRANSFORMER SECONDARIES PER 240.21 |
| 09/17/2003 |
ELECTRIC - PROGRESS |
|
Partial Approval |
IVRS - Inspection 0000* |
| 09/11/2003 |
ELECTRIC - PROGRESS |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 07/16/2003 |
ELECTRIC - PROGRESS |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ANSWERED QUESTIONS FOR CONTRACTOR 2) ABOVE SERVICE TO STRUCTURAL CEILING IS DEDICATED ELECTRICAL SPACE AS PER 110.26 |
| 05/06/2003 |
ELECTRIC - PROGRESS |
|
Partial Approval |
IVRS - Inspection 0000*OK 1ST LIFT IN BLOCK. |