Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM05923
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/03/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
02/26/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NEED H.D. BOLTS AT GARAGE KWIK BOLT OK 2) AT FRONT DOOR NEED 5/8" DIAMETER EPOXY BOLTS (FOR HTT22) 3) MOVE PEX 12" MINIMUM FROM CAN LIGHTS LIVING ROOM 4) HTLTI PINS AT 3" ON CENTER 5) WATER HEATER FLU NO LESS THAN 60 DEGREE ANGLE 7" RISE PER FEET THRU-OUT LIVING ROOM 5) 3 FIXTURES ON 1/2" 2ND FLOOR BATH 6) TUB SURROUND NOT SECURED 2ND FLOOR 7) NO DWV TEST 8) GAS PRESSURE OK |