Permit: T02CM05916

Parcel: 136154340


Addresses:

7737 E ROGET DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/18/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ 1) OK FOR FINAL 2) LEFT GAS CARD
08/16/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ELEC DISCONNECT ON ROOF HAS NO FUSES, THEREFORE, THE CIRCUIT BREAKER IS THE OVER CURRENT PROTECTION. 40 AMP IS TOO LARGE. 35 AMP IS MAX. CHANGE BREAKER
08/09/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) THE CONDENSATE CONNECTION TO THE LAV TAIL PIECE IS BACK PITCHED. PROVIDE A HOSE CLAMP AT CONNECTION TO PVC 2) DISCONNECT ON ROOF IS NOT ACCESSIBLE. RELOCATE AS NEEDED. RECALL FOR INSPECTION 3) ALSO DO NOT USE WHITE FOR LINE VOLTAGE ON A/C CIRCUIT. REPLACE WIRE