Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ 1) OK FOR FINAL 2) LEFT GAS CARD | |
| 08/16/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ELEC DISCONNECT ON ROOF HAS NO FUSES, THEREFORE, THE CIRCUIT BREAKER IS THE OVER CURRENT PROTECTION. 40 AMP IS TOO LARGE. 35 AMP IS MAX. CHANGE BREAKER |
|
| 08/09/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) THE CONDENSATE CONNECTION TO THE LAV TAIL PIECE IS BACK PITCHED. PROVIDE A HOSE CLAMP AT CONNECTION TO PVC 2) DISCONNECT ON ROOF IS NOT ACCESSIBLE. RELOCATE AS NEEDED. RECALL FOR INSPECTION 3) ALSO DO NOT USE WHITE FOR LINE VOLTAGE ON A/C CIRCUIT. REPLACE WIRE |