Permit: T02CM05903

Parcel: 112050450


Addresses:

2109 E HEDRICK DR


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM05903

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
09/10/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
09/08/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ BE ADVISED: PER PLAN SHEET EO. ELECTRICAL SPECS, PARAGRAPH 2 RACEWAYS: THE METHOD SPECIFIED BY THE ENGINEER FOR WIRING OF THIS PROJECT IS EMT CONDUIT AND CONDUCTORS. THE USE OF MC CABLE IS NOT MENTIONED IN THE SPECS. PLEASE SECURE A LETTER FROM THE ENGINEER OF RECORD STATING HIS CONSENT ALLOWING MC CABLE IN LEIU OF SPECIFIED CONDUIT/RACEWAY.