Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/25/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) OK ROUGH ELECTRIC |
| 09/24/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 08/18/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PROVIDE PROTECTION FOR CABLE AT TOP PLATE WHERE LESS THAN 1/4" TO EDGE 300-4 2) DATA TO BE INDEPENDENTLY SUPPORTED 300.11 3) SUPPORT NM CABLE OFF OF COPPER LINES 4) CIRCUITS TO BE RUN AS PER PLANS OR REVISE PLANS |