Permit: T02CM05880

Parcel: 13323111R


Addresses:

199 N PANTANO RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM05880

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2003 MECHANICAL - FINAL Approved OK FOR C OF O.
08/01/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PERMANENTLY LABEL EQUIPMENT ON ROOF 2) PAINT EXPOSED PVC WITH LATEX PAINT 3) PROVIDE INSTALL INSTRUCTIONS FOR A/C UNITS 4) OK FOR TEMP C OF O
07/30/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) UNDER SIDE OF FIRE DAMPER PENETRATIONS MUST BE INSTALLED PER SPECS. 2) PROVIDE ACCESS DOORS TO ALL FIRE DAMPERS 3) FIRE CAULK ALL VOIDS THRU OPENING
07/28/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) COULD NOT FIND SUPERINTENDENT OR MECHANICAL CONTRACTOR ON SITE
07/23/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) NEED TO SEE FIRE DAMPER OPENINGS, CONDENSATE DRAIN LINES