Permit: T02CM05880

Parcel: 13323111R


Addresses:

199 N PANTANO RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM05880

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
07/16/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK PANELS LP3, LP4, LP8 2) BOND ENCLOSURES 3) SUPPORT M/C CABLE/RELOCATE CABLE AS PER 334.10 AND 300.11 4) FINISH EMERGENCY LIGHTING 5) ROOMS #121, 122 AND 127 OK
07/14/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK COLUMN LINE 1-4 EXCEPT AS NOTED: SUPPORT WIRES ARE NEEDED FOR EXISTING SIGNS, INSTALL EMERGENCY RECESSED LIGHTING, OK TO ENERGIZE PANELS H.P5, LP6, LP7 AND VERIFY 600 VOLT RATING FOR WIRES IN CONTROL CABINET
07/11/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
07/09/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK WALL 1ST FLOOR, OK STAIRS WELL WALLS, OK TEMP POWER FOR TEST- CONTRACOTR HAS LOCK OUT/TAG PROCEDURE ON SITE AND INFORCE FOR POWER. ENERGIZE ONLY A/C PANEL. CALL FOR INSP BEFORE ENERGIZING OTHER PANEL.
1) FINISH ITEMS #1 OF INSP DATED 7/3/03 2) TRANSFORMER TO BE INSTALLED AS PER 450-13(b)
07/03/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* 1) FACTORY/RELOC CABLE TO BE SUPPORTED AS M/L CABLE 12" FROM BOX AND EVERY 6' 334-10 AND AT BOTH END 300-11 2) FIXTURE CLIPS TO BE 100 % EFFECTIVE AS PER CITY AMENDMENT TO 410-16 3) SUPPORT WIRE TO BE ON OPPOSITE CORNERS OF FIXTURES. OK WALLS ROOM # 116, 117, 103
07/01/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK NORTH WALL-OK SOFFITS 2) CHECK INSIDE SOFFIT FROM TOP LATER
06/27/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
06/26/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
06/24/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK COLUMN LINE 2 AND 3 RECEPTACLES ON COLUMNS
06/23/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
06/20/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
06/13/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*SOUTH OUTER WALL OK.OK ROUGH IN. ABOVE CEILING CONDUITS, J-BOXES, TRAPEZE FOR AC UNIT FEEDER CONDUITS.
06/06/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK WALLS ROOM # 121, 122/124-127, 129-133 AND 135-137
05/30/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
05/21/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK TEMP WIRING AND RECEPTACLES/LIGHT FOR USE