Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM05880
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/28/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
07/16/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK PANELS LP3, LP4, LP8 2) BOND ENCLOSURES 3) SUPPORT M/C CABLE/RELOCATE CABLE AS PER 334.10 AND 300.11 4) FINISH EMERGENCY LIGHTING 5) ROOMS #121, 122 AND 127 OK | |
07/14/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK COLUMN LINE 1-4 EXCEPT AS NOTED: SUPPORT WIRES ARE NEEDED FOR EXISTING SIGNS, INSTALL EMERGENCY RECESSED LIGHTING, OK TO ENERGIZE PANELS H.P5, LP6, LP7 AND VERIFY 600 VOLT RATING FOR WIRES IN CONTROL CABINET | |
07/11/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
07/09/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALL 1ST FLOOR, OK STAIRS WELL WALLS, OK TEMP POWER FOR TEST- CONTRACOTR HAS LOCK OUT/TAG PROCEDURE ON SITE AND INFORCE FOR POWER. ENERGIZE ONLY A/C PANEL. CALL FOR INSP BEFORE ENERGIZING OTHER PANEL. 1) FINISH ITEMS #1 OF INSP DATED 7/3/03 2) TRANSFORMER TO BE INSTALLED AS PER 450-13(b) |
|
07/03/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) FACTORY/RELOC CABLE TO BE SUPPORTED AS M/L CABLE 12" FROM BOX AND EVERY 6' 334-10 AND AT BOTH END 300-11 2) FIXTURE CLIPS TO BE 100 % EFFECTIVE AS PER CITY AMENDMENT TO 410-16 3) SUPPORT WIRE TO BE ON OPPOSITE CORNERS OF FIXTURES. OK WALLS ROOM # 116, 117, 103 | |
07/01/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK NORTH WALL-OK SOFFITS 2) CHECK INSIDE SOFFIT FROM TOP LATER | |
06/27/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
06/26/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
06/24/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK COLUMN LINE 2 AND 3 RECEPTACLES ON COLUMNS | |
06/23/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
06/20/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
06/13/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*SOUTH OUTER WALL OK.OK ROUGH IN. ABOVE CEILING CONDUITS, J-BOXES, TRAPEZE FOR AC UNIT FEEDER CONDUITS. | |
06/06/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK WALLS ROOM # 121, 122/124-127, 129-133 AND 135-137 | |
05/30/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
05/21/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK TEMP WIRING AND RECEPTACLES/LIGHT FOR USE |