Permit: T02CM05877

Parcel: 117031400


Addresses:

836 N 10TH AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/10/2003 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
09/05/2003 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection 0000*/ 1) GAS PRESSURE HOLDING AT 15 POUNDS 2) 140,000 BTU WITHOUT FURNACE 40' RUN IS GOOD FOR 171 CFH, NEED BTU RATING OF FURNACE FOR CALC 3) NEED BATH FLUES WATER HEATER AND FURNACE, ALSO COMBUSTION AND RELIEF DUCTS 4) CONC. IN TUB TRAP 5) SECURE COPPER WATER INSIDE AT FRONT BEDROOM
08/28/2003 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*/1) INADEQUATE TEST ON DWV SYSTEM. 2) PAD ALL WEATHERLINES PENETRATING STEEL FRAMING. 3) SOME MECHANICAL REGISTERS NEED ADDITIONAL SUPPORT. 4) NAIL PROTECT PENETRATIONS LESS THAN 1-1/4" FROM FACE OF FRAME. 5) FINISH FRAMING AROUND WINDOWS.