Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/14/2004 |
MECHANICAL - INTERMEDIATE |
|
Approved |
|
| 07/16/2003 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ PROVIDE MIN. 1/8" PER FT. SLOPE ON CONDENSATE DRAIN LINE. SUPPORT HORIZONTAL SECTIONS EVERY 4'. REMOVE SCREEN FROM DRYER VENT T-TOP. PROVIDE MIN. 1" CLEARANCE FROM WATER HEATER VENT. |