Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM05874

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/14/2004 MECHANICAL - INTERMEDIATE Approved
07/16/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ PROVIDE MIN. 1/8" PER FT. SLOPE ON CONDENSATE DRAIN LINE. SUPPORT HORIZONTAL SECTIONS EVERY 4'. REMOVE SCREEN FROM DRYER VENT T-TOP. PROVIDE MIN. 1" CLEARANCE FROM WATER HEATER VENT.