Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02CM05793

Parcel: 13728060A


Addresses:

5498 S PINTA AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/26/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/19/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) GROUND METAL ELECTRIC BOXES 2) NAIL PROTECT ALL WIRES WITHIN 1 1/4" OF STUD SURFACES 3) INSTALL SMOKE DETECTORS 4) INSTALL BUSHING IN METAL KNOCK OUTS