Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/23/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/22/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/18/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) GFI RECEPTACLE ON ROOF (OFF SET NIPPLE CANNOT BE ONLY MEANS OF SUPPORT FOR BOX) SUPPORT BOX 2) DISCONNECT FOR A/C UNIT CANNOT BE BLOCKED BY A/C NEED 36" IN FRONT OF 99' NEC 110.26 |
| 03/03/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FINISH A/C INSTALLATIOON #4 PREVIOUS INSP |