Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T02CM05789
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/22/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection :CAN NOT HAVE 3" COPPER CAN NOT TOUCH ANY METAL STUDS CHECK REVENT ABOVE CEILING |
|
07/19/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) NOT READY FOR INSPECTION | |
07/19/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) OVERHEAD VENTS REQUIRE A HANGER EVERY 4'-0" 2) 1 1/2" OVERHEAD VENT IN MAIN RESTROOM STILL HAS BACK PITCH 3) OVERHEAD WATER DISTRIBUTION IS OK AND WASTE AND VENT SYSTEM IN ROOM #110, 111, 112, 132, 127, 122, 138, 123 AND PARTIAL #124 LEAVE COILING OPEN |