Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM05789
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/18/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/OK C/O | |
11/17/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
10/15/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/NO COMPLIANCE WITH LAST INSP. WRITE-UP |
|
10/06/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : NOTES: 1) DISCONNECT SWITCHES AT AC #1 AND AC #13 IN VIOLATION OF WORKING CLEARANCE. 110-26 NEC. 2) NO LADDER FOR KITCHEN ROOF YET. |
|
08/20/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :OK KITCHEN ABOVE CEILING CALL FOR FINAL AFTER KITCHEN COMPLETE |
|
08/12/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ OK TEMP C OF O FOR STOCKING | |
08/06/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :notes: prior to c of o approval, light fixtures must be installed, bld to dark. make-up receipts, no loose or unterminated wires where may be in contact with personnel | |
08/03/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) OK TO CLEAR TEMP POWER FOR TEST SUBJECT TO BOND POSTING 2) CONTR TO BE RESPSONSIBLE TO LOCK OUT SERVICE TO UNAUTHORIZED PERSONAL | |
07/27/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) FOR TEMP POWER FOR TEST PROVIDE LETTER OF TORQUE FROM ELECTRIC, CONTR. FOR SES AFTER REVIEW OF VIDEO WITH CAMERA THRU UNDERGROUND FEEDER CONDUIT REVEALED FOREIGN OBJECTS IN CONDUIT, POSSIBLE DIRT. CONTR. TO PERFORM MEGGER TEST ON FEEDERS, SUBMIT TO ENGINEER FOR APPROVAL |