Permit: T02CM05789

Parcel: 13707045D


Addresses:

251 W IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM05789

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/OK C/O
11/17/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
10/15/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/NO COMPLIANCE WITH LAST INSP. WRITE-UP
10/06/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
NOTES: 1) DISCONNECT SWITCHES AT AC #1 AND AC #13 IN VIOLATION OF WORKING CLEARANCE. 110-26 NEC. 2) NO LADDER FOR KITCHEN ROOF YET.
08/20/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :OK KITCHEN ABOVE CEILING
CALL FOR FINAL AFTER KITCHEN COMPLETE
08/12/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ OK TEMP C OF O FOR STOCKING
08/06/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :notes: prior to c of o approval, light fixtures must be installed, bld to dark. make-up receipts, no loose or unterminated wires where may be in contact with personnel
08/03/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) OK TO CLEAR TEMP POWER FOR TEST SUBJECT TO BOND POSTING 2) CONTR TO BE RESPSONSIBLE TO LOCK OUT SERVICE TO UNAUTHORIZED PERSONAL
07/27/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) FOR TEMP POWER FOR TEST PROVIDE LETTER OF TORQUE FROM ELECTRIC, CONTR. FOR SES AFTER REVIEW OF VIDEO WITH CAMERA THRU UNDERGROUND FEEDER CONDUIT REVEALED FOREIGN OBJECTS IN CONDUIT, POSSIBLE DIRT. CONTR. TO PERFORM MEGGER TEST ON FEEDERS, SUBMIT TO ENGINEER FOR APPROVAL