Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/12/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 07/30/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) RECIEVED DOCUMENTATION FROM MONRAD ENGINEER FOR MEGGER TESTS AND UNDERGROUND VIDEO |
| 07/07/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) OK KITCHEN WALLS |
| 07/02/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) REMOVED MC FROM EMT AND TERMINATE PER LISTING 2) SUPPORT MC TO STRUCTURE EMT IS NOT APPROVED AS SUPPORT 3) OK EAST REST ROOMS 4) EXPOSE CONDUIT 3-2" CONDUIT FEEDERS UNDER SLAB, ALREADY POURED, AT LEAST 3 AREAS, NEED TO READ LETTERING |
| 06/29/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) OK REST OF MAIN BLD, CALL FOR KITCHEN AREA WHEN READY. 2) ALSO BE ADVISED THERE IS NO RECORD OF U.G. ELECTRICAL INSPECTIONS. |
| 06/25/2004 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) SUPPORT M/C CABLE WITHIN 12" OF BOXES. 2) TIGHTEN LOOSE FITTINGS. 3) SUPPORT CONDUITS WITHIN 3' OF BOXES. 4) FILL UNUSED OPENINGS IN BOXES. 5) JUNCTION BOXES TO BE BONDED. 250-148. |
| 06/21/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) OK WALLS SOUTH OF DEMIZING wall. 2) OK TO INSULATE CEILING SOUTH OF DEMIEZING WALL. |