Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T02CM05779

Parcel: 13323111R


Addresses:

199 N PANTANO RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/20/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK FINAL
08/13/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) LOOSE GROUND LUG 20 WE STILL HAVE COLOR CODING PROBLEMS 120/208 BLACK, RED, BLUE-WHITE AND 277/480 BROWN, ORANGE, YELLOW-GRAY
05/09/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*SENT TO TEP ON 5/12/03 @ 9:15AM OK TO CLEAR.